© 2018  IN-Power Co., Ltd All Rights    京ICP备05050896号-1   Powered By 300.cn

Super capacitor management system INPCMS

浏览量
编号:
Introduction
IN-Power super capacitor management system INPCMS is mainly used for the management of super capacitors, which realizes the functions of monitoring, management and protection for capacitor blocks.
时间
2018/07/31 15:47
我要询价
Product description
Technical parameters

Super capacitor management system INPCMS

 

IN-Power super capacitor management system INPCMS is mainly used for the management of super capacitors, which realizes the functions of monitoring, management and protection for capacitor blocks.  It plays a decisive role in the safety application and life extension of super capacitors used in groups.INPCMS includes three layers of architecture, namely, main control communication module INPCMS-COM, sampling module INPCMS-SAM, upper computer software INPCMS-SW or industrial control screen INPCMS-HIMI

 

Functional description

On-line monitoring

 • Voltage and temperature of capacitor modules

 • Individual over-voltage

 • Abnormal communication

 • CMS abnormal

 

HCI interface

 • Be provided with the function of alarm information collection, transfer, display and record

 

Real-time alarm function

 • On-site dry contact alarm output

 • Support the function of remote alarm and alarm content display

 

Protection

 • Individual over-voltage protection

 • Protection of over-temperature and too low temperature

 • Voltage protection of super capacitor module

 

Product features

 • Real-time acquisition of various states of the energy storage system super capacitor module, with sampling time <250μ

 • Strong active balancing function, ensuring the reliability of the system

 • Insulation performance up to 5000V, suitable for rail transit industry

 • Modular design is used for easy installation, use and maintenance; modules are isolated from each other with high reliability

 • Be provided with high performance, high reliability and real-time communication capability, and RS485/CAN communication mode is adopted to ensure accurate and timely report and release

 • HCI diagnosis or setting control strategy can be achieved

 • Be provided with the function of alarm information collection, transfer and record

 

System composition and wiring

 

Wiring diagram of the system

 
 
 

 • INPCMS can be connected in parallel with 16 INPCMS-COM modules

 • A single INPCMS-COM can carry 104 INPCMS-SAM modules for real-time information collection and communication, so as to realize the online software control.

 • RS485 communication mode is adopted between INPCMS-COM and INPCMS-SAM. Each system can detect the state of 1,664 super capacitor modules